Total Harmonic disortion (THDv) : <2% (Linear Load); <5% (non linear load)
Dynamic recovery time : 3 cycles at 90% of the static value
Admissible Overload : 110% for 10 min; 150% for 60 sec; > 160% for 200ms
Admissible Crest Factor : 3:1
Admissible Power Factor : 0.6-1 (inductive capacitive)
Imbalance Output voltage @ 100% unbalanced load : <1%
Total Harmonic disortion (THDv) : High Overload, short circuit : RMS voltage limit; High crest factor curent; Peak voltage limit
Lain-lain
Static bypass : Type : Solid state; Voltage : 380 VAC/400VAC (3Ph+N); Frequency : 50/60Hz; Activation Criterion : microprocessor control; Transfer Time : zero; Admissible overload : 150% for 1 Hour; 180% for 30 sec; > 200% for 200ms; Transfer to Bypass : Immediate for overloads above 160%; Retransfer : Automatic after alarm clear
Maintenance Bypass : Type : without interruption; Voltage : 380VAC/400VAC (3Ph+N); Freuency : 50/60 Hz
Operating Temperature : 0-35 C continuous running, 40 C 8-hour running at nomial input voltage, recharging batteries and no overload, 45 C derating to 85% with linear load