Voltage Output : 380V / 4000V / 415V; 3 phase + N + E, Backup Time 10 Minutes, Tower
Unit Utama
Spesifikasi
Form Factor
Tower
Back-Up Time Half Load
10 minutes
Voltase Masuk
Voltage input 380V / 400V/ 415V, 3 phase + E
Input Voltage 285V – 475V (L-L)
Rated Frequency 50Hz (46~54 Hz) / 60Hz (56~64 Hz)
Input current 69A / 100A
Dimensi Produk
455 x 830 x 1045mm
Voltase Keluar
Voltage Output 380V / 4000V / 415V, 3 phase + N + E
Frequency 50 Hz (Synchronizing up to ± 8%
Bypass voltage 165V (L-N) to 275V (L-N)
Nominal DC Voltage 384 Vdc
Rated voltage Output 380V / 4000V / 415V, 3 phase + N + E
Output P.f 0.8
Lain-lain
Voltage Distrotion (THDv) : ≤3% linear load / ≤8% non-linear load
Crest factor : 3:01
Overload Capability : 105% continuously with warning / 105% - 125% for 2mins before transfer to bypass; 150% for 30sec before transfer to bypass / >150% for 500ms before transfer to bypass
Display Interface : Push button, LCD & LED
Standard Isolation : Input, Bypass, Manual Bypass, Output and Battery MCB
LED Status Indicator : Utility Power. Battery discharge, Inverter ON